| CONNECTICUT STATE FIRE SAFETY CODE Sec. 4: Section 29-292-9d of the Regulations of Connecticut State Agencies is amended as follows: Chapter Seventeen, Section 17-3.2.2, of the Connecticut State Fire Safety Code is amended to read: (Amd) 17-3.2.2 Hazardous Areas. Any hazardous area shall be protected in accordance with Section 6-4. The areas described in Table 17-3.2.2 shall be protected as indicated. Where sprinkler protection without [fire rated} FIRE-RATED separation is used, areas shall be separated from other spaces by partitions complying with Section 6-3.2 with doors complying with Section 6-3.4. Table 17-3.2.2 Hazardous Area Protection
1Where storage areas not exceeding 24 sq ft (2.2 sq m) are directly accessible from the guest room or guest suite, no separation or protection shall be required. Exception: Residential-type heating appliances such as domestic hot water heaters, domestic furnaces, or domestic boilers may be unenclosed when located within an individual guest room or suite serving only that room or suite that is separated from all adjacent rooms or suites by construction having at least a ½-hr fire resistance rating. Order | Contact | Online Brochure | Brochure (pdf) | Home Copyright © 1999 - 2000 ConnCode Publications. All rights reserved. |
|