| CONNECTICUT STATE FIRE SAFETY CODE Sec. 3: Section 29-292-9d of the Regulations of Connecticut State Agencies is amended as follows: (NEW) Chapter Seventeen of the Connecticut State Fire Safety Code is amended by adding the following: (Amd) 17-2.4 Number of Exits. Not less than two exits shall be provided from every floor, including floors below the level of exit discharge and occupied for public purposes. Exception: Any building protected throughout by an approved, supervised automatic sprinkler system installed in accordance with Section 17-3.5 having four stories or less with not more than four guest rooms or guest suites per floor shall be permitted to have a single exit under the following conditions: (a) The stairway is completely enclosed or separated by barriers having a fire resistance rating of at least 1 hr with self-closing 1-hr fire protection-rated doors protecting all openings between the stairway enclosure and the building. (b) The stairway does not serve more than one-half story below the level of exit discharge. (c) All corridors serving as access to exits have at least a 1-hr fire resistance rating. (d) There is not more than 35 ft (10.7 m) of travel distance from the entrance door of any guest room or guest suite to an exit. (e) One-half-hr fire-rated horizontal and vertical separation between guest rooms or guest suites is provided. Order | Contact | Online Brochure | Brochure (pdf) | Home Copyright © 1999 - 2000 ConnCode Publications. All rights reserved. |
|